API RP 500, Ventilation
Free Area of Inlet Openings formula
\(\large{ A = \frac{ V }{ 1200 \; \sqrt{ \frac{ h \; \left( T_i \;-\; T_o \right) }{ T_i } } } }\) |
Where:
\(\large{ A }\) = free area of inlet (or outlet) opening (s)
\(\large{ V }\) = volume of building to be ventilated
\(\large{ h }\) = height from the center of the louver opening to the Neutral Pressure Level (NPL)
\(\large{ T_i }\) = temperature of indoor air
\(\large{ T_o }\) = temperature of outdoor air
Height from the center of the louver opening to the Neutral Pressure Level formula
\(\large{ h = \frac{ H }{ 1 \;+\; \left[ \left( \frac{ A_1 }{ A_2 } \right)^2 \; \left( \frac{ T_i }{ T_o } \right) \right] } }\) |
Where:
\(\large{ h }\) = height from the center of the louver opening to the Neutral Pressure Level (NPL). The NPL is the point on the vertical surface of a building where the interior and exterior pressures are equal.
\(\large{ H }\) = vertical distance (center to center) between A_1 and A_2
\(\large{ A_1 }\) = free area of lower opening
\(\large{ A_2 }\) = free area of upper opening
\(\large{ T_i }\) = temperature of indoor air
\(\large{ T_o }\) = temperature of outdoor air